NIOSH Standards

Established by NIOSH, the performance intent for firing range ventilation systems shall meet all the requirements outlined as recommendations and design considerations in HEW publication no. (NIOSH) 76-130, dated December, 1975, entitled "Lead Exposure Design Considerations for Indoor Firing Ranges".  This design standard prefers an air flow velocity of 75 feet per minute average on the empty range.  This design has consistently provided for the compliance within the established federal standards for airborne inorganic lead concentration limits.  When properly executed, lead concentrations are consistently maintained below the action level of 30 micrograms per cubic meter (30ug/m3) in an area where the limit shall not exceed 50 micrograms of lead per cubic meter (50ug/m3) of air over a time weighted average of eight hours as measured at the respiration zone of the shooters and the range officer when firing from the firing booths per OSHA 29 CFR. 1910.1025 and 1926.62